JG Series Copper Connecting Terminal JG Series
Cable Lugs JG Series

JG Series Copper Connecting Terminal

DT Series copper connecting terminals are pressed from T2 copper bar and tin-plated. The closed oil-hole barrel traps lubricant during crimping to reduce crimp force and improve conductor fill. Used for heavy-power terminations on motors, switchgear busbars and transformer tap changers.

Terminal Material
T2 copper
Wire Range
10–600 kcmil / 6–300 mm²
Stud Size
M5 – M20
Surface Treatment
Tin-plated

JG Series JG Series Copper Connecting Terminal Specifications

Complete product dimensions and model selection.

Item No. Φ (mm) D (mm) d (mm) L (mm)
JG-10 6.2 8 5 38
JG-16 8.4 9 6 41
JG-25 8.4 10 7 46
JG-35 8.5 11 8 52
JG-50 8.5 13 10 54
JG-70 10.5 16 12 61
JG-95 10.5 18 14 66
JG-120 12.5 20 15 73
JG-150 12.5 23 17 77
JG-185 14.5 25 19 86
JG-240 16.5 27 21 93
JG-300 16.5 31 24 103
JG-400 18.5 34 26 113
JG-500 20.5 38 30 124
JG-630 22.5 45 35 140
JG-800 22.5 50 40 170

Product Structure & Dimensions

JG Series Copper Connecting Terminal structure and dimensions

Get a Quote

Send us your wire size, stud size and quantity — we reply within 24 hours.

Looking for JG Series JG Series Copper Connecting Terminal?

Contact our team for product specifications and quotation inquiries.

Contact Us

Frequently Asked Questions

What is the oil-hole in a DT Series copper cable lug?

The small hole in the bottom of the barrel is filled with crimping lubricant at the factory. During hydraulic crimping, the lubricant is forced into the conductor strands, reducing crimping force and improving strand-to-barrel electrical contact.

What wire sizes does the DT Series cover?

6–300 mm² (10 AWG – 600 kcmil).

What stud sizes are available?

M5 through M20, covering motor terminal posts, busbar bolts and transformer tap-changer studs.

What is the material and plating?

Pressed from T2 (99.9 % pure) copper and tin-plated for corrosion protection.

Should DT lugs be used with aluminium cable?

No. Use DTL bimetal lugs for aluminium cable; copper lugs on aluminium cable cause galvanic corrosion.