DL Series Aluminum Cable Lug (Oil Blocking Type)
DL Series aluminium connecting terminals are pressed from 1060 aluminium bar. They are the usual choice for aluminium cable on distribution equipment where a copper lug would create a dissimilar-metal joint.
- Material
- 1060 aluminium bar
- Wire Range
- 10–630 mm²
- Type
- Oil-stop aluminium lug
- Application
- Aluminium cable termination
DL Series DL Series Aluminum Cable Lug (Oil Blocking Type) Specifications
Complete product dimensions and model selection.
| Item No. | Φ (mm) | D (mm) | d (mm) | L (mm) | L1 (mm) | W (mm) | S (mm) |
|---|---|---|---|---|---|---|---|
| DL-10 | 8.8 | 10 | 5.2 | 65 | 32 | 16 | 2.5 |
| DL-16 | 8.8 | 11 | 6.1 | 70 | 34 | 16 | 3.0 |
| DL-25 | 8.8 | 12 | 7.1 | 75 | 37 | 18 | 3.2 |
| DL-35 | 10.8 | 14 | 8.5 | 85 | 41 | 20 | 3.6 |
| DL-50 | 10.8 | 16 | 9.8 | 90 | 43 | 23 | 4.0 |
| DL-70 | 13 | 18 | 11.5 | 102 | 50 | 26 | 4.5 |
| DL-95 | 13 | 21 | 13.5 | 112 | 54 | 28 | 5.0 |
| DL-120 | 14.8 | 23 | 15 | 120 | 56 | 30 | 5.5 |
| DL-150 | 14.8 | 25 | 17 | 126 | 58 | 34 | 6.0 |
| DL-185 | 17 | 27 | 18.6 | 133 | 60 | 37 | 6.5 |
| DL-240 | 17 | 30 | 21.5 | 140 | 63 | 40 | 7.0 |
| DL-300 | 21 | 34 | 24 | 158 | 70 | 45 | 9.0 |
| DL-400 | 21 | 38 | 27 | 175 | 75 | 52 | 10.0 |
| DL-500 | 21 | 45 | 30 | 190 | 80 | 60 | 11.0 |
| DL-630 | 21 | 50 | 34.2 | 225 | 90 | 78 | 12.0 |
Product Structure & Dimensions
Get a Quote
Send us your wire size, stud size and quantity — we reply within 24 hours.
Looking for DL Series DL Series Aluminum Cable Lug (Oil Blocking Type)?
Contact our team for product specifications and quotation inquiries.
Frequently Asked Questions
What are DL Series lugs used for?
DL lugs terminate aluminium cable on distribution equipment. The body is pressed from 1060 aluminium bar so the lug and the conductor are the same metal, which avoids the galvanic corrosion that appears when aluminium cable is clamped in a copper lug.
Which cable sizes does DL cover?
From 10 mm² to 630 mm² in fifteen steps, matching DT one for one: DL-10 through DL-630. Barrel bore d, outer diameter D, palm width W and thickness S are listed for each size so the lug can be checked against the terminal chamber.
Why not simply use a copper lug on aluminium cable?
Copper and aluminium form a galvanic couple. In the presence of moisture the aluminium becomes the anode and corrodes, the joint resistance climbs and the connection overheats. A DL lug keeps the same metal throughout; where the equipment stud is copper, use a DTL bimetallic lug instead.
Do I need jointing compound when crimping DL lugs?
Yes, on aluminium conductors it is normal practice to wire-brush the strands and apply jointing compound before crimping. The compound displaces air and oxide from between the strands, which is what keeps the joint stable over time.
How should DL lugs be crimped?
Use a hexagonal crimper with the die for the cable size, crimp from the palm end towards the cable entry, and do not re-open the die mid-cycle. Aluminium work-hardens faster than copper, so a second bite in a different position is more likely to crack the barrel.
Are DL lugs RoHS compliant?
The 1060 aluminium body contains no restricted substances and the lugs meet RoHS and REACH requirements. Stud hole, palm width and barrel length can be adjusted for OEM programs.